Building Technology Experience Center concept air conditioning concept heat pump special energy-saving techniques in hydraulics Concrete core conditioning
Initial situation Passive House Technology Experience Center, Sino-German Ecopark Qingdao General requirements for a passive house: primary energy consumption < 120 kwh/(m² a) air tightness < 0,6 1/h high levels of energy efficiency in all technical installations minimum electricity consumption of pumps and fans Additional requirements in this project: climatic conditions high athmospheric moisture, high temperatures diverse/varying utilization units congress, office, accomodation, fitness center, cafe/restaurant
Aim Realization of passive house-standard with corresponding engineering concept: central ventilation system with the following tasks: - heating - cooling - dehumidifying heat generation and refrigeration by the use of water to water heat pump (photovoltaics)
Air conditioning concept
Multiple use of air Passive House Technology Experience Center, Sino-German Ecopark Qingdao supply air (external air) mixed air (overflowing supply air) exhaust air à Not every room needs fresh air in best air - quality! Advantages: less expense for the treatment of external air reduced volume flow short drain pipes
air current in the building
ventilation room
room ventilation supply air according to the concept of induction active chilled beams à High induction: intensive mixing of supply air with room air.
air flow in the offices
Parameters Passive House Technology Experience Center, Sino-German Ecopark Qingdao acceptable conditions for the rooms in summer: - external air 30 C - 90% RH - 24,4 g/kgh room air 26 C - 60% RH - 12,0 g/kgh heat pump: heating OR cooling dimensioning of boreholes à thermal response test photovoltaic installation
ventilation unit construction of device
ventilation unit construction of device rotation recuperator Energy recovery: 0,80 Humidity recovery: 0,80 SFP-Wert: 1.260-2.150 Ws/m³
ventilation unit construction of device plate preheater Energy recovery: 0,60
ventilation unit construction of device - winter
ventilation unit construction of device - summer
ventilation unit construction of device
Heatpumps : either heating OR cooling
2 different levels of temperature in summer: 7/12 C and 16/19 C
saving power in hydraulic systems
example indoor pool Stolberg: optimization of hydraulics saves 70% of energy for the pumps
diffuser after continuous flow machine pump Passive House Technology Experience Center, Sino-German Ecopark Qingdao stilling route + constant extension speed 3 to 5 m/s dynamic pressure 0,4 to 1,2 mws total discharge head 5 % to 20 % impact losses (turbulences)
indoor pool Stadionbad outdoor pool Stadionbad
1. all Pumps with VFD technology to modulate the flowrate 2. using butterfly valves
strainers and swing check valve one dimension higher than pipe-dimension
3. If there is more difference than 1 dimension between pump-outlet and pipe-system using diffusors if possible Self-made professionell
4. Using Balancing valves
CONCRETE CORE CONDITIONING
Concrete core condition System of room conditioning