small, speedy, safe Eextremely modular Up to 64 modules per bus de Quick reaction time: up to 20 µs A new Member of the Cube Family Murrelektronik s modular I/O system expands the field-tested Cube family with ather product line that is extremely useful. Designed in the same compact shape, it s highly flexible like all our Cube modules. The small modules are only millimeters wide and modularly designed, which saves space. Connections are also quick and easy to make thanks to the integrated backplane with power supply. Bus des for are available for all standard fieldbus protocols. I/O Modules Bus Nodes / Power Modules protection Function Modules protection Page 4.3.1 Page 4.3.3 Digital Inputs protection Digital Outputs protection Page 4.3.4 Page 4.3.5 Analog Inputs protection Analog Outputs protection Page 4.3.7 Page 4.3.9 Accessories Page 4.3.10
Bus Nodes Power module included Order Data Art-No. Art-No. Art-No. DP 57101 DeviceNet 57107 CANopen 57104 Fieldbus Operating modes Sync- and freeze mode are supported Transfer rate max. 12 Mbit/s max. 500 kbit/s max. 1 Mbit/s Addressing DIP switch Connector SUB-D9 5 pin Open-Style Connector SUB-D9 I/O capacity with modular expandability by up to 64 I/O modules and function modules Output Output voltage (I/Os /Backplane) 24 V DC/5 V DC Output current (I/Os /Backplane) 10 A/3 A Supply voltage Operating voltage 24 V DC (EN 61131-2) Sensor-system/actuator supply via terminal Current consumption max. 95 ma via BUS Monitoring - voltage Actuator warning Connection Spring clamp plug-in terminals: max. 1.5 mm² (max. 10 A) 48.5
Bus Nodes Power module included Order Data Art-No. Art-No. Art-No. Art-No. PROFINET IO 57106 EtherNet-IP 57105 EtherCAT 57103 Modbus TCP 57108 Fieldbus Operating modes Sync- and freeze mode are supported Transfer rate max. 100 Mbit/s Addressing DIP/DCP DIP/DHCP automatic Connector 2 RJ45 1 RJ45 I/O capacity with modular expandability by up to 64 I/O modules and function modules Output Output voltage (I/Os /Backplane) 24 V DC/5 V DC Output current (I/Os /Backplane) 10 A/3 A Supply voltage Operating voltage 24 V DC (EN 61131-2) Sensor-system/actuator supply via terminal Current consumption max. 95 ma via BUS Monitoring - voltage Actuator warning Connection Spring clamp plug-in terminals: max. 1.5 mm² (max. 10 A) 48.5
Power supplies Potential distributor Order Data Art-No. Art-No. Art-No. 8 24 V DC 57120 8 0 V DC 57121 4 24 + 4 0 V DC 57122 Supply voltage Operating voltage max. 30 V DC max. 0 V DC max. 30 V DC Total current max. 10 A Connection Spring clamp terminals: 0.08...2.5 mm² (AWG 28...12) 52.5
Power supplies for external voltage supply for external voltage supply and internal backplane Order Data Art-No. Art-No. Power module 57130 57131 Technical Data Operating voltage max. 28.8 V DC Total current max. 10 A Output Output current (I/Os /Backplane) 10/0 A 4 A/2 A Output voltage (I/Os /Backplane) 24 V AC 24 V DC/5 V DC Supply voltage Operating voltage max. 28.8 V DC Total current max. 10 A max. 6 A Connection Spring clamp terminals: 0.08...2.5 mm² (AWG 28...12)
Digital inputs Order Data Art-No. DI2 (E) 57220 DI4 - (E) 57240 DI8 - (E) 57280 Internal communication Module supply via system connection Current consumption max. 55 ma Input Sensor supply US 24 V DC, (EN 61131-2), max. 500 ma Type n-switching (EN 61131-2) Input filter 3 ms Galvanic isolation 500 V DC between inputs and internal communication via BUS Monitoring - voltage 0...+60 C (storage temperature -20...+70 C) Connection Spring clamp plug-in terminals: max. 1.5 mm² (AWG 16)
Digital outputs Order Data Art-No. DO2 - (E) 57320 DO4 - (E) 57340 DO8 - (E) 57380 Internal communication Module supply via system connection Current consumption max. 55 ma Output Actuator supply UA 24 V DC, (EN 61131-2), max. 1 A Switching current per output max. 0.5 A (short-circuit and overload protected) Galvanic isolation 500 V DC between outputs and internal communication Lamp load 5 W Output delay time 175 ns via BUS Monitoring - voltage Connection Spring clamp plug-in terminals: max. 1.5 mm² (AWG 16)
Digital outputs - 2A - 230VAC (Relays) Order Data Art-No. Art-No. DO2 - (E) 57325 57327 DO4 - (E) 57345 Internal communication Module supply via system connection Current consumption max. 60 ma max. 130 ma Output Actuator supply UA 24 V DC, (EN 61131-2), max. 4 A max. 30 V DC/230 V AC Switching current per output max. 2 A (short-circuit and overload protected) max. 3 A (short-circuit and overload protected) Galvanic isolation 500 V DC between outputs and internal communication Lamp load 10 W via BUS Monitoring - voltage Connection Spring clamp plug-in terminals: max. 1.5 mm² (AWG 16)
Analog inputs Voltage Current Voltage Order Data Art-No. Art-No. Art-No. AI2 - (E) 57231 57232 57233 AI4 - (E) 57261 57263 Internal communication Module supply via system connection Current consumption max. 60 ma from system, max. 25 ma externally (UI) max. 60 ma from system, max. 15 ma externally (UI) max. 60 ma from system, max. 25 ma externally (UI) Technical Data Operating voltage 24 V DC (20.4...28.8 V DC) EN 61131-2 Input Conversion time (analog) 480 ms (all channels) Resolution (analog) 15 Bit + sign Accuracy max. ±0.2 % max. 0.3 % max. ±0.2 % Connection Differential voltage input Differential current input Differential voltage input Voltage inputs Input resistor 200 kohm 200 kohm Input range 0...10 V DC -10 V DC...+10 V DC Current input signals Load max. 60 Ohm, (EN 61131-2) Input range 0...20 ma, 4...20 ma via BUS Monitoring - voltage Wire break upper/lower limit overload and BUS Connection Spring clamp plug-in terminals: max. 1.5 mm² (AWG 16)
Analog inputs (TH) for thermo elements (RTD) for resistors and temperature Order Data Art-No. Art-No. AI2 - (E) 57230 AI4 - (E) 57265 Internal communication Module supply via system connection Current consumption max. 75 ma from the system, max. 30 ma externally (UI) max. 75 ma Technical Data Operating voltage 24 V DC (20.4...28.8 V DC) EN 61131-2 24 V DC (EN 61131-2) Input Conversion time (analog) max. 4.2...324.1 ms (per channel) max. 330 ms (per channel) Type B, C, E, J, K, L, N, R, S, T Pt100, Pt1000, Ni100, Ni1000, R 0...3000 Ohm Resolution (analog) 15 Bit + sign Accuracy max. ±0.3 %, cold junction compensation 0.7...1.4 % Connection 2-wire input; TH+x, TH-x 2-wire (4 input); 3-, 4-wire (2 input) via BUS Monitoring - voltage Wire break upper/lower limit overload per channel and BUS 0...+55 C (storage temperature -20...+85 C) Connection Spring clamp plug-in terminals: max. 1.5 mm² (AWG 16)
Analog outputs Voltage Order Data Art-No. Art-No. Art-No. Art-No. AO2 - (E) 57331 57333 AO4 - (E) 57361 57363 Internal communication Module supply via system connection Current consumption max. 60 ma from system, max. 25 ma externally (UI), idle load Technical Data Operating voltage 24 V DC (20.4...28.8 V DC) EN 61131-2 Output Conversion time (analog) 200 ms (all channels) Resolution (analog) 15 Bit + sign Accuracy max. 0.5 % max. 0.2 % Galvanic isolation 500 V DC between inputs and internal communication Voltage output signals Load 5 kohm Input range 0...10 V DC -10 V DC...+10 V DC via BUS Monitoring - voltage Actuator warning and BUS Wire break upper/lower limit overload and BUS Connection Spring clamp plug-in terminals: max. 1.5 mm² (AWG 16)
Connection accessories Art-No. Bus cover Black plastic 57190 Shield bus carrier Black plastic Quantity: 10 pcs. 57191 Bus Connection Plug 90 SUB-D9 (male), screw terminals SUB-D9 (female), screw terminals CANopen 55762 55760 Bus Connection Plug 180 SUB-D9 (male), cut clamps, rigid cable SUB-D9 (male), cut clamps, flexible cable 55584 55583 Bus Connection Plug 90 SUB-D9 (male), cut clamps, rigid cable SUB-D9 (male), cut clamps, flexible cable 55585 55587 Bus Connection Plug 90 SUB-D9 (male), cut clamps, rigid cable, programming device conn. SUB-D9 (male), cut clamps, flexible cable, programming device conn. 55586 55588 Bus Connection Plug 90 SUB-D9 (male); M12 1, B-coded 7000-99441-0000000